求华为3900的外部告警(如停电、门禁)如何定义
用MML查询和定义(搜索 环境 )
BTS3900(R9以上,含R9)交流停电做在 UPEU上 2端口 65220 数字端口 低电平
BTS3900(老版本,R9以下) 交流停电做在 GTMU上 10端口 65521
门禁的没做过,你可以看一下历史告警里面的门禁告警编码是多少,找一个做了门禁告警的3900来参考参考
3900告警一般站点有8路,一次是 门禁,市电,油机,模块,低压,空调,红外,振动。
脚本是下面的,最后的电平值可以改的(如果反的话),需要和站上督导进行核对。
SET BTSENVALMPORT: IDTYPE=BYNAME, BTSNAME="某站名", CN=0, SRN=0, SN=19, PN=0, SW=OPEN, AID=65041, PT=BOOL, AVOL=HIGH;
SET BTSENVALMPORT: IDTYPE=BYNAME, BTSNAME="某站名", CN=0, SRN=0, SN=19, PN=1, SW=OPEN, AID=65042, PT=BOOL, AVOL=HIGH;
SET BTSENVALMPORT: IDTYPE=BYNAME, BTSNAME="某站名", CN=0, SRN=0, SN=19, PN=2, SW=OPEN, AID=65043, PT=BOOL, AVOL=LOW;
SET BTSENVALMPORT: IDTYPE=BYNAME, BTSNAME="某站名", CN=0, SRN=0, SN=19, PN=3, SW=OPEN, AID=65044, PT=BOOL, AVOL=LOW;
SET BTSENVALMPORT: IDTYPE=BYNAME, BTSNAME="某站名", CN=0, SRN=0, SN=19, PN=4, SW=OPEN, AID=65045, PT=BOOL, AVOL=LOW;
SET BTSENVALMPORT: IDTYPE=BYNAME, BTSNAME="某站名", CN=0, SRN=0, SN=19, PN=5, SW=OPEN, AID=65046, PT=BOOL, AVOL=LOW;
SET BTSENVALMPORT: IDTYPE=BYNAME, BTSNAME="某站名", CN=0, SRN=0, SN=19, PN=6, SW=OPEN, AID=65047, PT=BOOL, AVOL=LOW;
SET BTSENVALMPORT: IDTYPE=BYNAME, BTSNAME="某站名", CN=0, SRN=0, SN=19, PN=7, SW=OPEN, AID=65048, PT=BOOL, AVOL=LOW;